Empower and Tabreed bills explained

A district cooling bill from Empower, Tabreed or Emicool is not an electricity bill with a different logo. Half of it, often more, is a fixed charge for capacity you have reserved, and it does not fall when you use less cold. Here is how the bill is built, what that means for any attempt to cut it, and the one line on it worth checking before you spend a dirham.

7 min read


Most villa owners in Dubai never see a district cooling bill. Their air conditioning runs on their own split or ducted units, and the cost arrives as kilowatt-hours on the DEWA bill. But if you live in a tower, in many apartment communities, or in some of the villas on Palm Jumeirah, your cooling arrives as chilled water through a pipe, and it is billed separately by a cooling provider. In Dubai that is mostly Empower, which serves more than 80% of the city’s connected district cooling capacity. In Abu Dhabi it is mostly Tabreed, and Emicool covers areas such as Dubai Investments Park and Sports City.

The bill looks simple and is not. It has two parts that behave in completely different ways, and confusing them is the reason so many people are surprised that using less cooling barely moves the total.

The two halves of the bill

Consumption charge. This is the cold you actually used, measured in refrigeration ton-hours, written RT·h or TRh. One refrigeration ton is 3.517 kW of cooling, so one RT·h is 3.517 kWh of heat removed from your home. Our engine uses Empower’s rate of 0.568 AED per RT·h. This part goes up in summer, down in winter, and responds to everything you do.

Capacity charge. This pays for the cooling capacity reserved for your property, whether you use it or not. It is priced per refrigeration ton per year; our engine uses 750 AED per RT a year for Empower and 775 for Tabreed. A property contracted at 14 RT pays 10,500 AED a year in capacity before it has cooled a single room. Add a meter charge of about 30 AED a month and that is the floor of the bill.

A worked example: a 250 m² home on Empower

This is the standard district cooling case in our calculation engine: a 250 m² property on Empower, contracted at 14 RT, using an average of 1,700 RT·h a month. The engine spreads that across the year using the load shape of a typical UAE villa.

Line on the billHow it is calculatedPer year
Capacity charge14 RT × 750 AED10,500 AED
Meter charge30 AED × 12 months360 AED
Consumption20,400 RT·h × 0.568 AED11,587 AED
Total22,447 AED

Before VAT and any other items your provider or building adds. Check the names and rates on your own bill; tariffs vary by project.

Over the year, 48% of this bill is fixed. And the share swings with the seasons, which is why winter bills feel so stubborn:

MonthCold usedConsumptionFixedBillFixed share
January1,054 RT·h599 AED905 AED1,504 AED60%
July2,414 RT·h1,371 AED905 AED2,276 AED40%

In January you are using less than half the cold you use in July, and the bill is only a third lower. That is not an error on the meter. It is the capacity charge doing exactly what it was designed to do.

Why using less cold saves less than you expect

Here is the same property with the measures we would normally fit on a villa: solar control film on the glass, seals on the external doors, a smart thermostat in each of its five cooling zones, and a reflective coating on the roof. Figures are in survey mode, the conservative number we would put in a contract, with no change to the cooling contract.

MeasureSaving, survey mode
Solar control film on the glass1,181 AED / yr
Smart thermostats, five zones950 AED / yr
Seals on external doors633 AED / yr
Reflective roof coating393 AED / yr
All four together3,157 AED / yr

That is 27% of the consumption half, but only 14% of the whole bill, because the capacity charge does not move. In marketing mode, the top of the honest range, the same work saves 3,970 AED a year, or 18% of the bill.

There is one way district cooling is better for this kind of work than electricity. On DEWA, the heat you keep out is first divided by the efficiency of your air conditioner; our engine assumes a COP of 3.0. On district cooling, the provider sells you delivered cold, so every kilowatt-hour of heat you keep out is billed directly:

  • District cooling, Empower: 0.568 AED ÷ 3.517 = about 0.16 AED per kWh of heat kept out.
  • DEWA, top slab with fuel surcharge: 0.44 AED ÷ 3.0 = about 0.15 AED per kWh of heat.
  • DEWA, the 4,001 to 6,000 kWh slab: 0.38 AED ÷ 3.0 = about 0.13 AED per kWh of heat.

So each unit of heat you block is worth a little more on district cooling. The total percentage looks worse only because the fixed half dilutes it.

The line worth checking first: contracted capacity

Divide the cold you use in a year by the capacity you are contracted for, and you get the number of hours a year the property would have to run at full contracted load to use it all. In our example that is 20,400 RT·h ÷ 14 RT, about 1,457 hours out of the 8,760 in a year. Our engine flags anything below 1,500 hours as capacity that is probably set too high for what the property actually draws.

If the contracted load could be reduced by 3 RT, the capacity charge would fall by 3 × 750, or 2,250 AED a year, with no work on the building at all. Set against the retrofit, the arithmetic is blunt:

ScenarioSurvey modeMarketing modePayback, survey
Retrofit, contract unchanged3,157 AED / yr (14%)3,970 AED / yr (18%)over 10 years
Contract reduced by 3 RT only2,250 AED / yr2,250 AED / yrno outlay
Retrofit and contract reduced by 3 RT5,407 AED / yr (24%)6,220 AED / yr (28%)about 6 years

Whether a reduction is possible, and how much, is for the provider and whoever holds the cooling contract to decide. In many buildings that is the developer or the owners’ association rather than the individual unit. We cannot promise it will be granted, and we will not put a contract reduction into a savings guarantee. But it is the first question we would ask, because it costs nothing to ask.

Our honest advice for district cooling homes

  • Start with the contract, not the building. Work out your utilisation hours from twelve months of bills. If they are well under 1,500, ask about the contracted load before you pay anyone to fit anything.
  • Do not judge a measure by the percentage off the total. On district cooling, judge it against the consumption half. A 14% cut in the total can be a 27% cut in the cold you buy.
  • Thermostats and seals come first. They are the cheapest per dirham saved in our example; seals pay back in about four years and thermostats in about five and a half, in survey mode.
  • Roof coating rarely pays on the bill alone if the roof is already insulated. Our article on insulating paint and roof coatings explains why.

If your villa is on DEWA, none of this applies

Nearly all villa communities in Dubai, including Arabian Ranches, the Springs, the Meadows, Mira, Damac Hills, Mudon and Town Square, are chiller-free: each house cools itself and pays DEWA. There is no capacity charge, no RT·h and no contract to renegotiate. Every kilowatt-hour saved comes off the top slab, and the full ranking of measures by payback is on how to reduce a high DEWA bill.

Our online calculator is built for DEWA villas. If you are on district cooling, the survey is where the real figure comes from: send us twelve months of bills with the contracted load shown, and we will tell you whether the building or the contract is the better place to start. Rates per square metre are on the pricing page.